Air cooled water chiller and heat pump

with axial fans and scroll compressor HRCF R407C

Cooling capacity: 38-50.6 kW

Heating capacity: 44.2-58.8 kW
R407C


HRCF/HCF Unit 40 45 50
NOMI NAL COOLING CAPACITY* kW 38 43.4 50.6
NOMINAL HEATING CAPACITY** kW 44.2 50.4 58.8
HERMETIC COMPRESSOR / Scroll
Nº OF COMPRESSOR / CIRCUIT / 2/2 2/2 2/2
COOLING INPUT POWER kW 5.2X2 7.04 X 2 7.5X2
HEATING INPUT POWER kW 5.7X2 7.2 X 2 8.0X2
Axial fan
AIR FLOW: m3/h 16500 18700 21800
NOMINAL POWER INPUT X Nº kW × nº 0.55X2 0.55 X2 0.55X2
EVAPORATOR / Plate heat exchanger
WATER FLOW m3/h 7 7.7 9
WATER SIDE PRESSURE LOSS bar 0.62 0.66 0.70
DIAMETER OF HYDRAULIC CONNECTION inch 3/2" 3/2" 3/2"
REFRIGERANT / R407c
CHARGE AMOUNT kg 8 X 2 9 X 2 10 X 2
POWER SUPPLY V/Ph/Hz 400/3/50
MAX. POWER INPUT kW 6.89 7.54 8.33
MAX. CURRENT A 11.65 12.62 14.7
STARTING CURRENT A 63 63.1 73.5
SOUND PRESSURE LEVEL*** dB(A) 60 62 65
WATER STORAGE TANK VOLUME L 80 80 80

* Ambient air temperature 35℃, evaporator water temperature inlet/outlet 12/7 ℃;
** Ambient air temperature 7℃ DB, 6℃ WB; condenser water temperature inlet/outlet 40/45℃;
*** Sound pressure level measured at distance of 1 m and a height of 1.5 m above the ground in a free field (fan side)