Air cooled water chiller and heat pump
with axial fans and scroll compressor HRCF R407C
 |
Cooling capacity: 38-50.6 kW
Heating capacity: 44.2-58.8 kW |
| R407C |
| HRCF/HCF |
Unit |
40 |
45 |
50 |
| NOMI NAL COOLING CAPACITY* |
kW |
38 |
43.4 |
50.6 |
| NOMINAL HEATING CAPACITY** |
kW |
44.2 |
50.4 |
58.8 |
| HERMETIC COMPRESSOR |
/ |
Scroll |
| Nº OF COMPRESSOR / CIRCUIT |
/ |
2/2 |
2/2 |
2/2 |
| COOLING INPUT POWER |
kW |
5.2X2 |
7.04 X 2 |
7.5X2 |
| HEATING INPUT POWER |
kW |
5.7X2 |
7.2 X 2 |
8.0X2 |
| Axial fan |
| AIR FLOW: |
m3/h |
16500 |
18700 |
21800 |
| NOMINAL POWER INPUT X Nº |
kW × nº |
0.55X2 |
0.55 X2 |
0.55X2 |
| EVAPORATOR |
/ |
Plate heat exchanger |
| WATER FLOW |
m3/h |
7 |
7.7 |
9 |
| WATER SIDE PRESSURE LOSS |
bar |
0.62 |
0.66 |
0.70 |
| DIAMETER OF HYDRAULIC CONNECTION |
inch |
3/2" |
3/2" |
3/2" |
| REFRIGERANT |
/ |
R407c |
| CHARGE AMOUNT |
kg |
8 X 2 |
9 X 2 |
10 X 2 |
| POWER SUPPLY |
V/Ph/Hz |
400/3/50 |
| MAX. POWER INPUT |
kW |
6.89 |
7.54 |
8.33 |
| MAX. CURRENT |
A |
11.65 |
12.62 |
14.7 |
| STARTING CURRENT |
A |
63 |
63.1 |
73.5 |
| SOUND PRESSURE LEVEL*** |
dB(A) |
60 |
62 |
65 |
| WATER STORAGE TANK VOLUME |
L |
80 |
80 |
80 |
* Ambient air temperature 35℃, evaporator water temperature inlet/outlet 12/7 ℃;
** Ambient air temperature 7℃ DB, 6℃ WB; condenser water temperature inlet/outlet 40/45℃;
*** Sound pressure level measured at distance of 1 m and a height of 1.5 m above the ground in a free field (fan side) |